A gas suppression system only protects a room if the gas stays in the room. If the enclosure leaks, the extinguishing agent escapes before it can put out the fire, and the system fails exactly when it is needed. A room integrity test, also called a door fan test, is the proven way to check that your FM200 or clean agent room can hold the agent for the required time.
For data centres, telecom rooms, control rooms, substations and archives across Saudi Arabia, this test is a key step before handover and a smart part of ongoing maintenance.
What Is a Room Integrity Test?
A room integrity test measures how airtight a protected enclosure is. A calibrated fan is fitted into a doorway and used to pressurise or depressurise the room, and the airflow needed to hold a set pressure is measured. From these readings, the leakage area of the room is calculated, and software uses it, along with the room height and the design concentration, to predict how long the agent will stay at the required level.
Why Integrity Testing Is Important
- System performance: the agent must stay at or above the design concentration for the required hold time, commonly 10 minutes under NFPA 2001, so the fire is fully extinguished and cannot reignite.
- Compliance: acceptance requirements and project specifications commonly call for the test, and it is usually witnessed by the consultant or the Civil Defence representative.
- Protecting assets: servers, switchgear and critical records are costly or impossible to replace.
- Avoiding wasted discharge: a leaking room can mean a failed discharge test, an expensive agent refill and project delay.
Standards Behind the Test
Room integrity testing is based on recognised clean agent standards such as NFPA 2001, ISO 14520 and EN 15004, which describe the fan test method and the hold time requirement. Project specifications may add further requirements, so always follow the approved specification for your site.
How the Door Fan Test Is Done
- Room preparation: the room is set up as it would be in a fire condition, with dampers closed and openings sealed or set to their operating positions.
- Fan installation: an adjustable frame with a calibrated fan is fitted into the doorway.
- Pressure test: the fan pressurises and depressurises the room, and flow readings are taken at multiple pressures.
- Calculation: the equivalent leakage area is calculated, and the predicted agent hold time is generated from the room data.
- Leak identification: if the room fails, leak locations are traced using smoke or a pressure difference.
- Reporting: a clear report gives the room details, readings, calculated hold time and pass or fail result.
Common Leak Points in Protected Rooms
- Unsealed cable and pipe penetrations
- Partition walls that stop at the false ceiling instead of the slab
- Ducts, grilles and dampers that do not close fully
- Raised floor and ceiling void junctions
- Worn door seals, gaps below doors and unsealed door frames
- Electrical conduits and cable trays passing through walls
When Should You Test?
- At commissioning: before system handover and acceptance.
- After modifications: any new cable, pipe, duct or partition changes the room.
- Periodically: many operators retest regularly, often annually, to confirm the room still holds.
- After a failed test: to confirm the room passes once leaks have been sealed.
The same test applies to other gaseous agents too, including inert gas and fluorinated ketone systems, not only FM200.
Who Needs Integrity Testing in Saudi Arabia?
Data centres, telecom exchanges, server rooms, control and command rooms, power and substation rooms, banks, hospitals, museums, archives and industrial facilities all use gas suppression and benefit from regular integrity testing.
Why Manycon for Integrity Testing in Saudi Arabia
Manycon Contracting Company provides room integrity and door fan testing in Saudi Arabia as part of our specialist testing services, alongside passive fire protection and firestop. Our trained team uses calibrated equipment, follows recognised standards and issues clear reports ready for consultant and Civil Defence review. Our scope is testing and leak identification, so you get an independent, accurate result. Sealing works can then be carried out by the responsible contractor and the room retested.
Frequently Asked Questions
What is the difference between a door fan test and a discharge test? A door fan test uses air to measure leakage and predict hold time, with no gas released. A discharge test releases the real agent, which is costly and wasteful, so a fan test is the preferred method.
How long does a room integrity test take? Most rooms take one to a few hours depending on size, access and the number of leaks found.
What happens if the room fails? The leak locations are identified and reported. Once sealing is completed by the responsible contractor, the room is retested to confirm it passes.
Do I need to test if the room has not changed? Regular retesting is recommended because seals age and small changes build up over time. Follow your consultant, insurer and authority requirements.
Do you test rooms outside Riyadh? Yes, our team can mobilise across Saudi Arabia based on project requirements.